a. The isolating switch adopts three working positions design
b. Adopt contact design conducive to grounding closure.
c. high performance German Mubel disc spring, to ensure the stability of contact pressure.
d. The rotation isolation of the spindle drive has a small transmission gap to ensure reliable grounding and isolation break distance.
0577-62686971
Model composition
HWG(C)-40.5/T630
Operating conditions
installation site | In the box |
ambient temperature (℃) | -45~+140 |
height (m) | ≤2000 |
air humidity (%) | The daily average is not greater than 95% and the monthly average is not greater than 90% |
seismic intensity | No more than 8 degrees |
Technical parameters of isolating switch
order number | project | unit | numeric value |
1 | rated voltage | kV | 40.5 |
2 | rated frequency | Hz | 50 |
3 | rated current | A | 630 |
4 | Rated peak withstand current | kA | 50;63 |
5 | Rated short-term withstand current/time | kA/s | 20/4;25/4 |
6 | Rated short-circuit closing current (peak) | kA | 50/63 |
7 | mechanical life | Next | ≥5000 |
8 | 1min power frequency voltage: phase to ground/disconnected (in SF6 gas) | kV | 95/118 |
9 | Lightning impulse withstand voltage (peak) phase to ground/discharge (SF6 gas medium) | kV | 180/210 |
Mechanical characteristics of isolating switch
order number | project | unit | numeric value |
1 | Center-to-center distance | mm | 190 |
2 | Three-phase opening and closing at different periods | ms | ≤3 |
3 | Main circuit resistance | μΩ | ≤35 |