Hongwei-What you care about is what we care about
  • HWG(C)-40.5/T630 Isolation switch

HWG(C)-40.5/T630 Isolation switch

aThe isolating switch adopts three working positions design

b. Adopt contact design conducive to grounding closure.

chigh performance German Mubel disc spring, to ensure the stability of contact pressure.

dThe rotation isolation of the spindle drive has a small transmission gap to ensure reliable grounding and isolation break distance.


Service Hotline

0577-62686971

Model composition

HWG(C)-40.5/T630

 

Operating conditions

 installation site

In the box

 ambient temperature (℃)

-45~+140

 height (m)

≤2000

 air humidity (%)

The daily average is not greater than 95% and the monthly average is not greater than 90%

 seismic intensity

No more than 8 degrees

 

Technical parameters of isolating switch

 order number

 project

 unit

 numeric value

1

 rated voltage

kV

40.5

2

 rated frequency

Hz

50

3

 rated current

A

630

4

Rated peak withstand current

kA

50;63

5

Rated short-term withstand current/time

kA/s

20/4;25/4

6

Rated short-circuit closing current (peak)

kA

50/63

7

 mechanical life

Next

≥5000

8

1min power frequency voltage: phase to ground/disconnected (in SF6 gas)

kV

95/118

9

Lightning impulse withstand voltage (peak) phase to ground/discharge (SF6 gas medium)

kV

180/210

 

Mechanical characteristics of isolating switch

 order number

 project

 unit

 numeric value

1

Center-to-center distance

mm

190

2

Three-phase opening and closing at different periods

ms

≤3

3

Main circuit resistance

μΩ

≤35


Service Hotline

13738766792
  • logo
  • Production address:

    No. 333, Weishiqi Road, Yueqing Economic Development Zone, Zhejiang Province

  • Service hotline: 13738766792 Manager Xu 13777731466 Manager Xu
  • Email: 848160667@qq.com